Basic Info.
Application
Power, Electronic, Instrument, Lighting, Rectifier, Audio
Core
Core-type Transformer
Cooling Method
Dry-type Transformer
Winding Type
Two-winding Transformer
Certification
ISO9001-2000, ISO9001, CCC
Usage
Combined Transformer, Power Transformer, Distribution Transformer
Frequency Characteristics
High Frequency
Type
Power, Electric, Distribution Transformer
Name
Dry Type Transformer
Phase Number
There Phase Transformer
Core Materials
Silicon Steel
Winding Material
Copper/Aluminium Winding
Vector Group
Dyn11 or Yyn0 (Customized)
Use
Power Transformer, Distribution Transformer
Insulation Material
Cast Resin
Accessories
Cooling Fans, Enclosure ,Temperature Control
Frequency
50Hz or 60Hz High Frequency Transformer
Transformer Type
Cast Resin Dry Type Rectifier Transformer
Category
Electric Power Transformer /Isolation Transformer
Other Name
Voltage Transformer
Transport Package
Wooden Case Packing, Container Shipping
Product Description
Product Detail
1. Product Display
Our SC(B) series epoxy resin cast dry transformer is cast under vacuum with thin insulating bands automatically.
The core is made of a high-permeable grain-orientated silicon sheet and cast with imported epoxy resin.
The coil is reinforced with glass fiber and cast under vacuum with filler epoxy resin.
It has good mechanical properties, is free of crack and inner bubble, and has a low local discharge, high reliability and long service life.
The high and low-voltage systems are cast under vacuum, thus the coil will not absorb moisture, the clamps of the core are subjected to corrosion-resistant treatment and it may run under high temperature or other serious environments.2. Product Drawing
3. Product SpecificationModel | SCB10-1000 KVA-11/2*0.33KV |
Type | Dry Type Transformer |
Standard | IEC60076 |
Rated Power | 1000 KVA |
Frequency | 50 HZ |
Phase | Three |
Cooling Type | ANAF |
Primary Voltage | 11 KV |
Secondary Voltage | 2*0.33(LV1=0.33KV, LV2=0,33KV) |
Winding Material | Copper |
Vector Group | Yy0d11 |
Impedance | 6 |
Tap Changer | NLTC |
Tapping Range | ±2*2.5% |
No Load Loss | 1.9kw |
On Load Loss | 8.7kw |
Accessories | Cooling fans, Temperature controller, etc |
SCB12/13/14/18 10KV/0.4KV 100kVA-3150kVA
High Voltage:10(6,6.3,10.5,11)KV Connection Symbol:D,yn11 or Y,yn0 Rated Frequency:50Hz/60Hz Low Voltage:0.4(0.415,0.433)KV Tapping Range of HV:±2x2.5% Insulation Level:LI75 AC35/AC3 |
Rated power (KVA) | Short-Circuit Impedance(%) | SC(B)18 (W) | SC(B)14 (W) | SC(B)12/13 (W) | No-Load Current (%) | Sound pressure dB(A) | Weight (kg) | Inner Dimension(mm) | Overall Dimension(mm) |
| No-Load Loss | On-Load Loss75ºC | No-Load Loss | On-Load Loss75ºC | No-Load Loss | On-Load Loss75ºC | L | W | H | L | W | H |
| 100 | 4 | 210 | 1120 | 245 | 1120 | 290 | 1240 | 1.5 | 45 | 590 | 1070 | 600 | 1160 | 1500 | 1100 | 2200 |
| 125 | 245 | 1320 | 290 | 1320 | 340 | 1460 | 1.3 | 46 | 740 | 1100 | 600 | 1200 | 1500 | 1100 | 2200 |
| 160 | 280 | 1510 | 330 | 1510 | 390 | 1680 | 1.3 | 46 | 810 | 1130 | 680 | 1240 | 1500 | 1100 | 2200 |
| 200 | 330 | 1800 | 380 | 1800 | 450 | 2000 | 1.1 | 46 | 890 | 1160 | 720 | 1250 | 1500 | 1100 | 2200 |
| 250 | 380 | 1960 | 445 | 1960 | 525 | 2180 | 1.1 | 46 | 1050 | 1220 | 720 | 1300 | 1500 | 1100 | 2200 |
| 315 | 465 | 2470 | 545 | 2470 | 640 | 2740 | 1.0 | 46 | 1250 | 1240 | 760 | 1260 | 1700 | 1300 | 2200 |
| 400 | 520 | 2840 | 605 | 2840 | 715 | 3150 | 1.0 | 46 | 1420 | 1260 | 830 | 1240 | 1700 | 1300 | 2200 |
| 500 | 610 | 3470 | 720 | 3470 | 845 | 3860 | 1.0 | 46 | 1530 | 1280 | 870 | 1200 | 1700 | 1350 | 2200 |
| 630 | 705 | 4180 | 830 | 4180 | 975 | 4650 | 0.9 | 48 | 1810 | 1330 | 880 | 1230 | 1700 | 1350 | 2200 |
| 630 | 6 | 680 | 4240 | 805 | 4240 | 945 | 4710 | 0.9 | 48 | 1760 | 1470 | 880 | 1180 | 1700 | 1350 | 2200 |
| 800 | 795 | 4950 | 940 | 4950 | 1105 | 5500 | 0.9 | 48 | 2090 | 1500 | 900 | 1130 | 1900 | 1350 | 2200 |
| 1000 | 930 | 5780 | 1095 | 5780 | 1290 | 6430 | 0.8 | 48 | 2500 | 1570 | 900 | 1220 | 1900 | 1350 | 2200 |
| 1250 | 1095 | 6890 | 1290 | 6890 | 1520 | 7660 | 0.8 | 48 | 2920 | 1610 | 900 | 1330 | 2100 | 1500 | 2200 |
| 1600 | 1290 | 8350 | 1515 | 8350 | 1780 | 9270 | 0.8 | 48 | 3650 | 1720 | 900 | 1420 | 2100 | 1500 | 2200 |
| 2000 | 1600 | 10280 | 1890 | 10280 | 2220 | 11420 | 0.7 | 50 | 4190 | 1780 | 980 | 1480 | 2300 | 1500 | 2200 |
| 2500 | 1890 | 12210 | 2230 | 12210 | 2620 | 13570 | 0.7 | 50 | 5400 | 2000 | 1020 | 1830 | 2300 | 1600 | 2200 |
| 3150 | 2340 | 14640 | 2695 | 14640 | 3100 | 16150 | 0.5 | 50 | 6730 | 2030 | 1270 | 2050 | 2350 | 1600 | 2200 |
| Note: The above parameters are only for designing and selecting reference, and the final parameters are subject to the actual product. |
SCB12/13/14/18 20KV/0.4KV 200kVA-3150kVA High Voltage::20(15,22,24)KV Connection Symbol:D,yn11 or Y,yn0 Rated Frequency:50Hz/60Hz Low Voltage:0.4(0.415,0.433)KV Tapping Range of HV:±2x2.5% Insulation Level:LI125 AC55/AC3 |
Rated power (KVA) | Short-Circuit Impedance(%) | SC(B)18 (W) | SC(B)14 (W) | SC(B)12/13 (W) | No-Load Current (%) | Sound pressure dB(A) | Weight (kg) | Inner Dimension(mm) | Overall Dimension(mm) |
| No-Load Loss | On-Load Loss75ºC | No-Load Loss | On-Load Loss75ºC | No-Load Loss | On-Load Loss75ºC | L | W | H | L | W | H |
| 200 | 6 | 390 | 2090 | 450 | 2090 | 530 | 2320 | 1.5 | 46 | 1250 | 1460 | 720 | 1350 | 1900 | 1350 | 2200 |
| 250 | 440 | 2430 | 520 | 2430 | 610 | 2700 | 1.3 | 46 | 1480 | 1490 | 720 | 1430 | 1900 | 1350 | 2200 |
| 315 | 510 | 2900 | 600 | 2900 | 710 | 3220 | 1.3 | 47 | 1550 | 1510 | 720 | 1470 | 2100 | 1400 | 2200 |
| 400 | 610 | 3450 | 710 | 3450 | 840 | 3820 | 1.1 | 48 | 1730 | 1550 | 720 | 1500 | 2100 | 1400 | 2200 |
| 500 | 710 | 4120 | 840 | 4120 | 980 | 4580 | 1.1 | 48 | 1980 | 1580 | 830 | 1550 | 2100 | 1400 | 2200 |
| 630 | 800 | 4870 | 950 | 4870 | 1110 | 5410 | 1.0 | 49 | 2280 | 1600 | 830 | 1600 | 2100 | 1500 | 2200 |
| 800 | 920 | 5870 | 1080 | 5870 | 1270 | 6530 | 1.0 | 50 | 3180 | 1730 | 830 | 1760 | 2300 | 1500 | 2200 |
| 1000 | 1080 | 6950 | 1280 | 6950 | 1500 | 7730 | 0.8 | 50 | 3580 | 1800 | 830 | 1780 | 2300 | 1500 | 2200 |
| 1250 | 1250 | 8180 | 1470 | 8180 | 1730 | 9090 | 0.8 | 52 | 3680 | 1820 | 900 | 1850 | 2400 | 1500 | 2200 |
| 1600 | 1460 | 9820 | 1720 | 9820 | 2030 | 10910 | 0.8 | 52 | 4680 | 1980 | 920 | 2040 | 2500 | 1600 | 2200 |
| 2000 | 1700 | 11600 | 2010 | 11600 | 2360 | 12880 | 0.7 | 53 | 5340 | 2200 | 960 | 2080 | 2700 | 1600 | 2200 |
| 2500 | 8 | 2030 | 13720 | 2400 | 13720 | 2810 | 15250 | 0.7 | 53 | 6480 | 2330 | 990 | 2170 | 2800 | 1700 | 2200 |
| 3150 | 2510 | 16330 | 2840 | 16330 | 3320 | 18150 | 0.6 | 54 | 7530 | 2360 | 1270 | 2250 | 2800 | 1700 | 2200 |
| Note: The above parameters are only for designing and selecting reference, and the final parameters are subject to the actual product. |
SCB12/13/14/18 35KV/0.4KV 200kVA-3150kVA High Voltage: 35(33,38.5)KV Connection Symbol:D,yn11 or Y,yn0 Rated Frequency:50Hz/60Hz Low Voltage: 0.4(0.415,0.433)KV Tapping Range of HV:±2x2.5% Insulation Level: LI200 AC85/AC3 |
Rated power (KVA) | Short-Circuit Impedance(%) | SC(B)18 (W) | SC(B)14 (W) | SC(B)12/13 (W) | No-Load Current (%) | Sound pressure dB(A) | Weight (kg) | Inner Dimension(mm) | Overall Dimension(mm) |
| No-Load Loss | On-Load Loss75ºC | No-Load Loss | On-Load Loss75ºC | No-Load Loss | On-Load Loss75ºC | L | W | H | L | W | H |
| 200 | 6 | 470 | 2360 | 540 | 2360 | 640 | 2630 | 1.5 | 51 | 1550 | 1590 | 920 | 1790 | 2300 | 1600 | 2200 |
| 250 | 520 | 2700 | 610 | 2700 | 720 | 3010 | 1.3 | 51 | 1750 | 1590 | 920 | 1860 | 2300 | 1600 | 2200 |
| 315 | 620 | 3210 | 730 | 3210 | 850 | 3570 | 1.3 | 51 | 1950 | 1650 | 850 | 1750 | 2400 | 1700 | 2200 |
| 400 | 730 | 3850 | 850 | 3850 | 1000 | 4280 | 1.1 | 51 | 2200 | 1840 | 890 | 1800 | 2400 | 1700 | 2300 |
| 500 | 850 | 4730 | 1010 | 4730 | 1180 | 5260 | 1.1 | 52 | 2640 | 1910 | 920 | 1800 | 2500 | 1700 | 2300 |
| 630 | 970 | 5480 | 1150 | 5480 | 1350 | 6090 | 1.0 | 52 | 2880 | 1970 | 930 | 2100 | 2600 | 1700 | 2400 |
| 800 | 1130 | 5830 | 1340 | 5830 | 1570 | 6480 | 1.0 | 52 | 3530 | 1980 | 1030 | 2030 | 2600 | 1800 | 2500 |
| 1000 | 1280 | 7400 | 1510 | 7400 | 1760 | 8230 | 0.8 | 52 | 4080 | 2070 | 1060 | 2070 | 2700 | 1800 | 2500 |
| 1250 | 1480 | 9040 | 1750 | 9040 | 2060 | 10040 | 0.8 | 53 | 4430 | 2080 | 1050 | 2080 | 2700 | 1800 | 2500 |
| 1600 | 1710 | 10960 | 2010 | 10960 | 2360 | 12180 | 0.8 | 53 | 5310 | 2150 | 1050 | 2180 | 2800 | 1800 | 2600 |
| 2000 | 2010 | 12960 | 2370 | 12960 | 2780 | 14390 | 0.7 | 54 | 6410 | 2300 | 1050 | 2250 | 2900 | 1800 | 2700 |
| 2500 | 8 | 2340 | 15500 | 2760 | 15500 | 3240 | 17230 | 0.7 | 55 | 7630 | 2400 | 1100 | 2230 | 3000 | 2000 | 2700 |
| 3150 | 2890 | 18590 | 3330 | 18590 | 3830 | 20510 | 0.6 | 55 | 7530 | 2500 | 1200 | 2350 | 3000 | 2000 | 2800 |
| Note: The above parameters are only for designing and selecting reference, and the final parameters are subject to the actual product. |
4. Product Structure
Product Process
Raw Materials Core Slitting Core Cutting
Core Stacking Insulating Curing HV Winding
LV Winding Pouring Drying
Assembly Testing Warehouse
Product Application
Dry-type transformers are widely used in various industries and applications that require high safety, reliability, and environmental compatibility. Some of the common applications of dry-type transformers are:
1 Chemical, oil, and gas industry: Dry-type transformers are used to supply power to various equipment and processes that involve flammable or explosive substances, such as refineries, petrochemical plants, pipelines, offshore platforms, etc.
2 Environmentally sensitive areas: Dry-type transformers are used to protect the environment from oil spills or leaks that can contaminate water sources, soil, or wildlife habitats, such as water protection areas, forests, wetlands, etc.
3 Fire-risk areas: Dry-type transformers are used to prevent fire hazards or minimize fire damage in areas that are prone to fire outbreaks or have strict fire regulations, such as indoor substations, underground substations, hospitals, schools, hotels, shopping malls, etc.
4 Renewable generation: Dry-type transformers are used to connect renewable energy sources to the grid or to the load, such as wind turbines, solar panels, hydroelectric plants, etc.
5 Other applications: Dry-type transformers are also used in other applications that require high performance, low maintenance, or special features, such as traction systems, marine systems, mining systems, data centers, etc.
Related Products
Company Profile
HeBei LeiCheng Since its inception, always adhere to the "quality first, credit first" business purpose, constantly develop innovative products, expand the market, and with many scientific research units, colleges and universities work closely and hired professional and technical personnel as guideline, USES the domestic and foreign advanced technology, experienced several years of hard struggle, finally achieved gratifying results, specifically Industry production of single-phase three-phase conversion power supply, control transformer, three coherent transformer, CNC machine tool control transformer, main transformers, power transformers, power transformers, special transformers, voltage regulator, voltage regulator, reactor, inverter, soft start and other CNC machine tools widely used, the company pays attention to the development of products, research and development at the same time, constantly strengthen the quality management.
Office Environment
Factory
Certifications
FAQ
1. Who we are ?
We are based in HeBei, China,sell to Domestic Market(80.00%),Southeast Asia(20.00%). There are all about 1200-1500 people in our company.
2.How can we guarantee quality?
Always make a final Inspection before shipping.
3.What can you buy from us?
110kV-220kV Oil-immersed Power Transformer,Dry-type Transformer,Unpacked H Grade Dry Transformer,Oil-immersed Distribution Transformer, Pad-mounted Transformer,Enameled Wire,Composite Wire,Transposed Wire,Paper Covered Wire,Film Wrapped Wire.
4.Why should you buy from us not from other suppliers?
As an enterprise specializing in transformer production, we have high quality, fast delivery, guarantee after-sales service and factory price. What's more, we have ISO9001-2008, OHSAS 18001:2007, ISO4001:2004L ,UL ,CE certificates and IEC, ANSI, KEMA, GOST standard.
5.What services can we provide?
Accepted Delivery Terms: FOB,CIF,EXW; Accepted Payment Currency:USD,CNY; Accepted Payment Type: T/T,L/C; Language Spoken:English,Chinese.
Address:
Room 1-2-3102, Wanda B1 South District, Yuhua District, Shijiazhuang, Hebei, China
Business Type:
Trading Company
Business Range:
Construction & Decoration, Electrical & Electronics, Industrial Equipment & Components, Manufacturing & Processing Machinery, Metallurgy, Mineral & Energy, Tools & Hardware
Management System Certification:
ISO 9001, ISO 14001, ASME
Company Introduction:
Our factory was founded in 2002, the factory is located in Guangzong County, Xingtai City, Hebei Province economic Development zone. Through thirteen years of careful management, our factory has developed into a private enterprise with a certain scale. The factory covers an area of more than 56, 000 square meters, and the plant construction area is 32, 000 square meters. There are more than 150 ordinary staff, more than 30 technical staff and 15 management personnel.
The factory is mainly divided into two departments, respectively producing electrical appliances and electrical equipment and products. Electric appliances include electric power accessories, standard parts, electric power fittings, etc. Power equipment includes dry transformers, oil transformers, high voltage switch components, outdoor high voltage vacuum circuit breakers, etc.
The factory has passed ISO9001 quality system certification and has environmental management system certification. Our products are produced in strict accordance with national standards, and can also be customized according to customer standards. Over the years, we have been adhering to the quality of survival, credibility to open up the market for the purpose. Welcome domestic and foreign merchants to visit our company, and win-win cooperation.